Go to global navigation

Read the article

Go to local navigation

Go to footer



Climate control equipment

Home > Climate control equipment > Indoor enclosure cooler "COOLCABI" lineup > Non-fluorocarbon Series Energy saving Lateral mounting

Non-fluorocarbon Series Energy saving Lateral mounting


High energy efficiency cuts electricity up to 67% from conventional products.
Wide input voltage from 100 to 240VAC

COOLCABI OCA-E

Features

Use environment Cooling system Function Obligatory inspection by Japanese law Specifications
Indoor Compressor
Energy saving mode Display function N/A Energy saving Wide input voltage Equipped with RS485

Certificates/Approvals

EU RoHS2 China RoHS CE UL CCC CSA PSE

Model/Specification

Model OCA-E600BC-AW OCA-E1000BC-AW
Type of mounting Lateral mounting
Cooling capacity *1 600W 1000W
Rated voltage(50/60Hz) *2 Single phase 100 to 240VAC
Rated current consumption*3 100V 2.1A 3.5A
200V 1.2A 1.8A
240V 1.1A 1.6A
Starting current 8.6A 15.3A
Power consumption 200W 340W
Working temperature *3 +20 to +55℃
Working humidity Not exceeding 85%RH, free from condensation
Noise 62dB (A) 65dB (A)
Temp. setting range *3 +30 to+45℃ (Default +35℃)
Display Internal temperature/Alarm code/Operation lamp (Green)/Alarm lamp (Red)
Function Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder, Forced cooling operation for inspection
Alarm output No-voltage contact output 1a x 2 (COMMON) 250VAC 2A 30VDC 2A
Communication function RS485 2-wire system (Modbus RTU)
Vibration withstand Vibration frequency10 to 55Hz, Amplitude 0.15mm, Sweep cycle 10 times
Protection category *4 Internal circuit IP54 equivalent
Conformity to standards Environment RoHS2
Refrigerant R1234yf(400g) R1234yf(700g)
GWP *4 <1
Color Powder coating N8 corresponding, N4 corresponding
Dimensions(mm) W300×H550×D240 W350×H650×D240
Weight 23kg 30kg
*1 Nominal value when both of internal and external temperatures are +35℃.
*2 The permissible voltage variation during operation is within +10% to -10% to the rated value, which means instantaneous variation and does not mean a supply voltage constantly input.
*3 Use only within the specified temperature range.
*4 By IPCC 5th Report 2013


Product lineup

OCA-E600BC-AW

OCA-H300BC-AW2

Cooling capacity

600W

A complete set of supply

●COOLCABI:1 pc.  ●Fixing bolt:4 pcs. ●Washer:4 pcs. ●Spring washer:4 pcs.
●Nut:4 pcs ●Packing:4m ●Drain hose:2m
●Alarm explanation sheet:1 pc. ●Instruction manual:1 copy

Consumable parts

Replacement fan Replacement filter
Internal fan FM-15035P-D48-01 CF-S12
External fan FM-15051P-D48-01

Performance diagram

Performance diagram

Dimensional drawing

外形寸法図

Mounting cutout

パネルカット図


OCA-E1000BC-AW

OCA-H600BC-A200

Cooling capacity

1000W

A complete set of supply

●COOLCABI:1 pc.  ●Fixing bolt:4 pcs. ●Washer:4 pcs. ●Spring washer:4 pcs.
●Nut:4 pcs ●Packing:4m ●Drain hose:2m
●Alarm explanation sheet:1 pc. ●Instruction manual:1 copy

Consumable parts

Replacement fan Replacement filter
Internal fan FM-15035P-D48-01 CF-S13
External fan FM-15051P-D48-01

Performance diagram

能力グラフ

Dimensional drawing

外形寸法図

Mounting cutout

パネルカット図


Cautions

・Locate the unit so as to assure good ventilation and distance of at least 200mm from the walls or other units.
 Failure to this may degrade cooling performance of the unit and cause condensation.
・Setting temperature should be basically at 35℃. Avoid setting at an unnecessarily low value.
・Electrical connection should be made via appropriate circuit breakers.
・This product is designed for indoor use only.
・Do not use this product in the following places.
 - A place where corrosive or flammable gases exist in the air, or where the insulation destruction occurs.
 - A place where the product may be subject to shock or vibration.
・Make sure that electrical wiring work is done by qualified electrician.
・Check for damage on packaging when the product is delivered. .Any packaging damage can lead to a cause of malfunction.
 Make sure that there is no damage on the package on delivery and contact your supplier, if any.